The Missus and I are packing for a 2 week trip to visit friends and relatives in Ohio and I realize it is getting warm in the house. Danged AC went out. I have a service contract but they can't get out until in the morning and we need to leave by noon to meet a commitment Sunday afternoon.
Hit 100 yesterday and today, not a good time to lose AC.
Why now, been working fine since we built in 2007???
could be a quick fix.....check your overflow pan in the attic....it has a float switch which will shut everything down.....outside unit and the blower in the attic....the way to tell if that is it is to try to run anything.....if nothing runs, most likely that is the problem.....you will have to blow out the P trap which is preventing the pan from draining....good time to replace air filters also.....I put the date on mine so I know how old they are....